Type of current Utilization category Typical application
AC AC-1 Non-inductive or low-inductive load, resistance furnaces
AC-2 Slipring motors: starting, switching off
AC-3 Suirrelcage motors: starting, switching off while running
AC-4 Squirrel-cage motors: starting, regenerative braking, reversing, jogging
AC-5a Switching gas discharge lamps
AC-5b Switching of incandescent lamps
AC-6a Switching of transformers
AC-6b Switching of capacitor banks
AC-8a Switching hermetically sealed cooling compressor motors with manual reset of the overload release
AC-8b Switching hermetically sealed cooling compressor motors with automatic reset of the overload release
DC DC-1 Non-inductive or low-inductive load, resistance furnaces
DC-3 Shunt motors: Starting, braking by reversal, inching, dynamic braking of DC motors
DC-5 Seriers motors: Starting, braking by reversal, inching, dynamic braking of DC motors
DC-6 Switching of incandescent lamps

หมวดหมู่การใช้งานสำหรับคอนแทคเตอร์เสริม ตามมาตรฐาน IEC / EN 60947-5-1

Type of current Utilization category Typical application
AC AC-12 Controlling ohmic and inductive loads when isolation through optocouplers is used
AC-13 Controlling semiconductor loads when isolation through transformers is used
AC-14 Controlling small electromagnetic loads (≤ 72 VA)
AC-15 Controlling small electromagnetic loads (≥ 72 VA)
DC DC-12 Controlling ohmic and electronic loads when isolation through optocouplers is used
DC-13 Controlling DC electromagnets
DC-14 Controlling electromagnetic loads with built-in economy resistors

 

หมวดหมู่การใช้งานสำหรับโหลดสวิตช์, ตัวตัดการเชื่อมต่อ, เบรกเกอร์ และเซฟตี้สวิทซ์ ตามมาตรฐาน IEC 947-3, EN 60947, DIN VDE 0660 ตอนที่ 107

Type of current Utilization category Typical application
AC AC-20A(B) 1) Making and breaking without load
AC-21A(B) 1 Switching of ohmic loads, including small overloads
AC-22A(B) 1) Switching of mixed ohmic and inductive loads, including small overloads
AC-23A(B) 1) Switchung of motors or other high-inductive loads
DC DC-20A(B) 1) Making and breaking without load
DC-21A(B) 1) Switching of ohmic load including little overload
DC-22A(B) 1) Switching of mixed ohmic and inductive load including little overload (eg. shunt motors)
DC-23A(B) 1) Switching of motors or other high inductive load (eg. inverse-speed motors)

1) A: frequent actuation, B: casual actuation

All the switchgears in our range of products are designed in accordance to VDE0660 for the utilization category AC-3. For the permissible power data, please see the respective options.